Capacity Curtailment on the AT-IT border for delivery day 21/07/2022

Published: 20/07/2022 | 07:26

1.TSO(s) *:

Swissgrid

2. Identification of affected Long Term Transmission Rights

Austria to Italy

3. Triggering event:

 

☒Curtailment to ensure operation remains within Operational Security Limits
☐Curtailment due to Force Majeure
☐Curtailment due to emergency situation
 

4. Affected volume in MW / hour for each concerned period:

Austria to Italy

21/07/2022  

 

07:00 – 08:00  204 MW

08:00 – 09:00  204 MW

12:00 – 13:00  204 MW

13:00 – 14:00  204 MW

14:00 – 15:00  204 MW

18:00 – 19:00  204 MW

19:00 – 20:00  204 MW

20:00 – 21:00  204 MW

21:00 – 22:00  204 MW

22:00 – 23:00  204 MW

23:00 – 24:00  204 MW 

 

5. Amount of LTTR remaining after curtailment:

Austria to Italy

21/07/2022  

 

07:00 – 08:00  183 MW

08:00 – 09:00  183 MW

12:00 – 13:00  185 MW

13:00 – 14:00  185 MW

14:00 – 15:00  185 MW

18:00 – 19:00  183 MW

19:00 – 20:00  183 MW

20:00 – 21:00  183 MW

21:00 – 22:00  179 MW

22:00 – 23:00  179MW

23:00 – 24:00  161 MW 

 

6. Information on exact operational security limit(s) that are expected to be violated in the absence of curtailment *:

 Expected overloading on 380kV Sils – Soazza;  Robbia-Gorlago + Robbia-S.Fiorano

7. Why alternative measures are not sufficient to avoid the expected violation of operational security limit(s) *?

 During the CC process, all the remedial actions provided by the TSOs are already considered by the CCC in the calculation.